Velan and Anchor Darling Double Disc Gate Valves on Safety Injection and Charging Systems - SealOE
Brands - AP Services
HOME | BRANDS | AP Services | sealOE™ | Case Studies Details
Velan and Anchor Darling Double Disc Gate Valves on Safety Injection and Charging Systems
Problem
Chronic packing leakage usually around the gland follower outer diameter has occurred due to large gland follower clearance (>0.030") on O.D. Stuffing box inside diameter also runs oversized by 0.008”-0.020”. Instances have occurred on Velan and Anchor Darling double disc gate valves.
Solution
Use a close tolerance high density carbon bushing above the packing set to close up clearances and prevent extrusion.